Investigation of Mechanical Properties and Corrosion Behaviour for 1010 Carbon Steel Pipes Used for Steam Boilers

  • Alaa ABOU HARB Polytechnic University of Bucharest
  • Ion CIUCA Polytechnic University of Bucharest
  • Bilel RAHALI Polytechnic University of Bucharest
  • Roxana-Alexandra GHEŢA Polytechnic University of Bucharest
Keywords: steam boilers pipes, carbon steel, corrosion rate, weight loss, hardness properties, tensile stress

Abstract

Depending on the conditions of their use, most equipment gets deteriorated in time. In this paper the corrosion rate (CR) was verified by using the experiment of weight loss (WL) of specimens from steam boiler pipes (SBP) made of 1010 carbon steel with a thickness of 4 mm. CR was calculated by specimens’ weight loss in the corrosive environment at 25 °C in 5% NaCl - 10% H2O2 solution which reproduces the environment in the plant during specific times. The mechanical properties which were verified include hardness test and tensile test. The results that have been obtained through tensile curves and hardness properties on specimens 1 and 2 were compared to a non-service specimen (3) made of 1010 carbon steel. It is concluded that there was an increase in the properties of tensile and a decrease of hardness for both specimens by comparing them with a non-service specimen. Due to overheating, a deposition of layers of lime (CaO) on the pipes was caused. It is noticed that the decrease of the mechanical properties leads to increased corrosion.

Creative Commons License

Downloads

Download data is not yet available.

References

[1]. ***, www.outokumpu.com.
[2]. Talbot D., Talbot J., Corrosion Science and Technology, Materials Science and Technology, CRC Pres., 1998.
[3]. Anthony U., Ikenna M., Ufuma O. B., Ezemuo D. T., Corrosion Rates and its Impact on Mild Steel in Some Selected Environments, Journal of Scientific and Engineering Research, 3(1), p. 34-43, 2016.
[4]. Marcus P., Introduction to the Fundamentals of Corrosion, Corrosion: Fund-Amentals, Testing, and Protection, vol. 13A, ASM Handbook, ASM International, p. 3-4, 2003.
[5]. Ahmad Z., Principles of Corrosion Engineering and Corrosion Control, Boiler Corrosion, Chapter 11, p. 576-608, 2006.
[6]. Al-hajri M., Al-muaili F., Andijani I., Mobin M., Muaili F., Corrosion of boiler tubes some case studies, published in the Proceeding Of 4th SWCC Acquired Experience Symposium held at Jeddah, p. 739-763, 2005.
[7]. Bayer G., Larkin E., Zamanzadeh M. Failure analysis and Investigation methods for boiler tube failures, Matco Associates, Inc. 4640 Campbells Run Road Pittsburgh, Pennsylvania 15205, 2007.
[8]. Jonas O., Boiler Tube Sampling and Inspection Procedures, Recommended Practices, Water Chemistry Control. Jonas, Inc., Wilmington, DE, 1992.
[9]. Mobin M., Malik A. U., Al-Hajri M., Investigations on the Failure of Economizer Tubes in a High-Pressure Boiler, J. Fail. Anal. And Preven., 8, p. 69-74, 2008.
[10]. ***, ASM metals handbook, vol. 1, Properties and Selection: Irons, Steels, and High-Performance Alloys, Sep 2005.
[11]. Mc Naughon, Kenneth J., the Staff of Chemical Engineering, Controlling Corrosion in Process Equipment, Materials Engineering II, McGraw – hill Publication Company, 1980.
Published
2017-03-15
How to Cite
1.
ABOU HARB A, CIUCA I, RAHALI B, GHEŢA R-A. Investigation of Mechanical Properties and Corrosion Behaviour for 1010 Carbon Steel Pipes Used for Steam Boilers. The Annals of “Dunarea de Jos” University of Galati. Fascicle IX, Metallurgy and Materials Science [Internet]. 15Mar.2017 [cited 23Dec.2024];40(1):47-1. Available from: https://gup.ugal.ro/ugaljournals/index.php/mms/article/view/1214
Section
Articles